Save up to 33% water and chemicals
The new generation Baltibond hybrid coating is the result of a continuous process improvement.
There are 3 good reasons to choose for the new generation Baltibond hybrid coating
1. Save money
- increase the service life of your evaporative cooling equipment
- reduce water consumption with higher cycles of concentration
- reduce chemical consumption with higher cycles of concentration
- Experience an economical alternative to SST 304L
A unit protected with the new generation Baltibond hybrid coating can operate at higher cycles of concentration and extended water quality limits. You can operate with the same cycles of concentration as a full stainless steel execution. This results in water and chemical savings up to 33%.
The effect of cycles of concentration on water and chemicals consumption.
2. Increase safety
The smooth surface finish
- reduces the development of biofilm
- facilitates internal cleaning
3. Respect the environment
- Reduce chemical and water rejection
- Reduce water consumption with higher cycles of concentration
To ensure long service life of your evaporative cooling equipment, we recommend you maintain the circulating water quality within the following limits.
Water Quality Mesure |
New generation |
Stainless Steel 304L |
Galvanized Steel |
---|---|---|---|
pH |
6.5 to 9.2 |
6.5 to 9.2 |
6.5 to 9.0 |
pH during initial passivation |
Below 8.2 |
Below 8.2 |
Below 8.2 |
Total hardness (as CaCO3) |
50 to 750 mg/l |
50 to 750 mg/l |
50 to 600 mg/l |
Total Alkalinity (as CaCO3) |
600 mg/l max. |
600 mg/l max. |
500 mg/l max. |
Total Dissolved Solids |
2050 mg/l max. |
2050 mg/l max. |
1500 mg/l max. |
Chlorides |
300 mg/l max. |
300 mg/l max. |
250 mg/l max. |
Sulfates* |
350 mg/l max. |
350 mg/l max. |
250 mg/l max. |
Conductivity |
3300 µS/cm |
3300 µS/cm |
2400 µS/cm |
Total Suspended Solids |
25 mg/l max. |
25 mg/l max. |
25 mg/l max. |
Chlorination (as free Chlorine) Continuous |
1,5 mg/l max. |
1,5 mg/l max. |
1 mg/l max. |
Chlorination (as free Chlorine) Batch dosing for cleaning & |
5-15 mg/l max. for 6 hours |
5-15 mg/l max. for 6 hours |
5-15 mg/l max. for 6 hours |
*Higher concentration of Sulfates is allowed, provided the sum of Chlorides + Sulfates parameters does not exceed 500 mg/l for galvanized steel, 650 mg/l for Baltibond/ SST 304L
Note: For Ozone water treatment application, Stainless Steel 316 execution is required. Ozone levels are to be maintained to 0.2 pmm +/- 0.1 ppm for at least 90% of the time, with absolute maximum peaks of 0.5 ppm.
Would you like to see the new generation Baltibond hybrid coating test sample coupons? Ask your BAC representative to show you the superior Baltibond hybrid coating quality.