REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvements, specifications, weights and dimensions are subject to change without notice.

General notes

1. All location dimensions for coil connections are approximate and should not be used for prefabrication of connection piping.
2. If discharge hoods with positive closure dampers are furnished, see table in section Engineering Data Straight Discharge Hood with PCD for added weight and height.
3. For external static pressure up to 125 Pa use next larger motor size.
4. For indoor applications of fluid coolers, the room may be used as a plenum with ductwork attached to the discharge only. If inlet ductwork is required, an enclosed fan section must be specified; consult your BAC representative for details.
5. Fan cycling results only in on-off operation. For additional steps of control, two-speed fan motors are available. More precise capacity control can be obtained with modulation fan discharge dampers or a Baltiguard® Drive System.
6. Make up, overflow, suction, drain connection and access door can be provided on side opposite to that shown; consult your BAC representative.
7. Shipping/operating weights indicated are for units without accessories such as sound attenuators, discharge hoods, plume abatement coils, etc. Consult factory certified prints to obtain weight additions and the heaviest section to be lifted.

Last update: 21/12/2024

VFL 24X-48X

VFL_24X_48X

1. Fluid in ND100; 2. Fluid out ND100; 3. Access door; 4. Make up ND25; 5. Overflow ND50 for VFL 24X and 36X and ND80 for VFL 48X; 6. Drain ND50; 7. Vent ND15

Model Weights (kg) Dimensions (mm) Air Flow (m³/s) Fan Motor (kW) Water Flow (l/s) Pump Motor (kW) Coil Volume (L)
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H
VFL 241-H 1950 1280 1280 3350 1250 1855 7.6 (1x) 4.0 5.9 (1x) 0.55 (1x) 176
VFL 242-H 2220 1460 1460 3350 1250 2015 7.4 (1x) 4.0 5.9 (1x) 0.55 (1x) 229
VFL 242-J 2230 1490 1490 3350 1250 2015 8.1 (1x) 5.5 5.9 (1x) 0.55 (1x) 229
VFL 243-J 2470 1670 1670 3350 1250 2230 7.9 (1x) 5.5 5.9 (1x) 0.55 (1x) 282
VFL 361-L 2800 1810 1810 4560 1250 1855 12.7 (1x) 11.0 9.0 (1x) 0.75 (1x) 258
VFL 361-M 2810 1820 1820 4560 1250 1855 13.8 (1x) 15.0 9.0 (1x) 0.75 (1x) 258
VFL 362-M 3130 2090 2090 4560 1250 2090 13.4 (1x) 15.0 9.0 (1x) 0.75 (1x) 338
VFL 363-K 3470 2280 2280 4560 1250 2350 10.8 (1x) 7.5 9.0 (1x) 0.75 (1x) 418
VFL 363-M 3540 2350 2350 4560 1250 2350 13.0 (1x) 15.0 9.0 (1x) 0.75 (1x) 418
VFL 481-M 3490 2170 2170 5480 1250 1855 15.1 (1x) 15.0 12.1 (1x) 1.1 (1x) 341
VFL 482-L 3930 2490 2490 5480 1250 2090 13.6 (1x) 11.0 12.1 (1x) 1.1 (1x) 448
VFL 483-L 4390 2830 2830 5480 1250 2350 13.4 (1x) 11.0 12.1 (1x) 1.1 (1x) 556
VFL 483-M 4400 2840 2840 5480 1250 2350 14.6 (1x) 15.0 12.1 (1x) 1.1 (1x) 556
VFL 484-M 4860 3170 3170 5480 1250 2560 14.3 (1x) 15.0 12.1 (1x) 1.1 (1x) 664