Engineering data

REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. All dimensions are in mm. Weights are in kg.
2. Unit should be continuously supported on a flat level surface.
3. H1,H2= installed height. Coil connections are closed and filled with inert gas for shipping and storage. Add 355 mm for shipping height.

Last update: 21/12/2024

TSU-M - TSU-LM

TSU-M_TSU-LM

1. Outlet; 2. Inlet; 3. Sight tube; 4. Access hatch.

Model Latent Capacity (kWh) Approx. Ship. Weight (kg) Approx. Oper. Weight (kg) Tank Water Volume (l) Coil Glycol Volume (l) Connection Size ND (mm) Unit Width (mm) Unit Length (mm) Unit Height (mm) H1 Tank Height (mm) H2)
TSU-237M 834 4420 17730 11320 985 50 2400 3240 2440 2390
TSU-476M 1674 7590 33530 22110 1875 80 2400 6050 2440 2390
TSU-594M 2087 9150 42200 28250 2320 80 2980 6050 2440 2390
TSU-761M 2676 10990 51610 34640 2990 80 3600 6050 2440 2390
TSU-L184M 647 3760 14360 8820 770 50 2400 3240 2000 1950
TSU-L370M 1301 6400 27060 17250 1460 80 2400 6050 2000 1950
TSU-L462M 1625 7710 34030 22030 1810 80 2980 6050 2000 1950
TSU-L592M 2082 9200 41560 27020 2280 80 3600 6050 2000 1950