REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This page includes data current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product improvement, specifications, weights and dimensions are subject to change without notice.

General notes

1. Access door is always opposite to inlet connection end.
2. Alternative inlet/outlet and tower configurations are available.
3. Nominal outlet connection size provided.
4. Actual outlet sized to match flow.
5. Models RCT 2218-1 and 2129-1 have direct drive motors.
6. Models RCT 2218-2 and 2129-2 have direct drive motors.
7. Triple fan units are not available with common FRP basin. Only for installation on concrete basin.

Last update: 21/12/2024

RCT 2118-1 - 2441-1

RCT_2118-1_2320-1

1. Water inlet; 2. Water outlet; 3. Drain; 4. Overflow; 5. Make up; 6. Quick fill; 7. Fan motor.

Model Weights (kg) Dimensions (mm) Air Flow (m³/s) Fan Motor (kW) Fluid Inlet ND (mm)
Oper. Weight (kg) Ship. Weight(kg) Heaviest Section (kg) L W H
RCT 2118-1 2675 1000 1000 2284 2284 3252 15.4 (1x) 5.5 (1x) 150
RCT 2129-1 2675 1000 1000 2284 2284 3252 17.3 (1x) 7.5 (1x) 150
RCT 2142-1 3375 1250 1250 2589 2589 3326 18.5 (1x) 5.5 (1x) 150
RCT 2156-1 3375 1250 1250 2589 2589 3326 20.4 (1x) 7.5 (1x) 150
RCT 2183-1 4125 1550 1550 2894 2894 3413 23.9 (1x) 7.5 (1x) 200
RCT 2208-1 4125 1550 1550 2894 2894 3413 27.2 (1x) 11.0 (1x) 200
RCT 2238-1 4850 1800 1800 3198 3198 3646 31.2 (1x) 11.0 (1x) 200
RCT 2262-1 4850 1800 1800 3198 3198 3646 34.2 (1x) 15.0 (1x) 200
RCT 2368-1 7300 2700 2700 4787 3198 4228 47.8 (1x) 18.5 (1x) 200
RCT 2386-1 7300 2700 2700 4787 3198 4228 50.2 (1x) 22.0 (1x) 200
RCT 2299-1 5700 2100 2100 3499 3499 3810 39.0 (1x) 15.0 (1x) 200
RCT 2320-1 5700 2100 2100 3499 3499 3810 41.8 (1x) 18.5 (1x) 200
RCT 2418-1 8500 3000 3000 5247 3500 4428 54.3 (1x) 18.5 (1x) 200
RCT 2441-1 8500 3000 3000 5247 3500 4428 57.3 (1x) 22.0 (1x) 200